Variance function - Benzo(a)pyren in drinking water

last update: 2010-07-09 |
| Range from: |
0.005 |
µg/l |
| to: |
0.2303 |
µg/l |
| Θ0: |
-4.9113 |
|
| Θ1: |
0.8537 |
|
| EU drinking water limit: |
0.01 |
µg/l |
| VCR, limit: |
29.96 |
% |
| NRV: |
9 |
|
| Ndata sets: |
76 |
|
For calculation of Θ0 and Θ1 concentrations were converted to kg/l.